SCR Charger

The charger is designed to charge the battery at a constant value regardless of changes in the AC power voltage or the discharge state of the battery so that the battery is not damaged by overcharging or overdischarging. In addition, the charger load is always supplied with a constant DC power supply, so that in the event of a commercial power outage, DC power is supplied from the storage battery to the load without an instantaneous power outage.

Features

Excellent voltage stability
– The output voltage is extremely stable , so if the input voltage is within ±10% and the load is between 20% and 100%, the DC output is kept within ±0.5% when the input voltage is within a constant load within 1%.

Easy to handle
– parts are well positioned and modular assembly facilitates handling of maintenance and operation etc.

Output voltage setting
– Floating and equal charging voltages are adjusted separately and the selection of floating and equal charging methods is performed by the selection switch.

Protection
– The rectifier for the charger provides overvoltage protection and overcurrent protection, and the limit for overcurrent is set by the factory to approximately 125% of the rated output current.

Principle of motion diagram

TDC Charger Electrical Characteristics

Chargers an item Scope of regulations Remark
Input voltage 380 / 220VAC ±15% / 220VAC ±15%
constant three phases / one phase
Frequency 60㎐ ±5% / 50㎐ ±5%
power factor P.F 0.8(LAG) and later
Output Rated current 15A/ 20A / 30A / 40A / 50A / 75A / 100A
(rectifying  module) or order specification
Rated voltage 48VDC(54VDC) or Order Specifications
Output voltage variable range 42V ~ 55V
Voltage stability Within ±1%
efficiency 80% or more Input (KW)/output (KW) × 100 at rated load
SID DROPPER(2nd  or 4th stage)
a storage battery Automatic charging function
Protection function Over voltage , low voltage protection / output over current protection
indicating instrument DIGITAL or ANALOGE Input voltage, output (storage battery) voltage/output (charging) current
Control Module an item Scope of regulations Remark
Environmental conditions Temperature of use 0 ~ 40℃
Storage temperature -20 ~ 70℃
humidity 0 ~ 90%

TDC Charger Production Model and Size

Formality Model Capacity Size (mm)
(W x D x H)
SCR Type a single
or three phase
TDC 4805 1Ø 0.4KVA 350 x 370 x 220
TDC 4810 1Ø 0.8KVA8
TDC 4815 1Ø 1.2KVA
TDC 4820 1Ø 1.6KVA
TDC 4825 1Ø 2KVA
TDC 4830 1Ø 2.4KVA
TDC 4835 1Ø 2.8KVA 270 x 470 x 500
TDC 4840 1Ø 3.2KVA
TDC 4845 1Ø 3.6KVA
TDC 4850 1Ø 4KVA
TDC 4855 1Ø 4.4KVA
TDC 4860 1Ø 4.8KVA
TDC 4865 3Ø or 1Ø 5.2KVA 340 x 530 x 580
TDC 4870 3Ø or 1Ø 5.6KVA
TDC 4875 3Ø or 1Ø 6KVA
TDC 4880 3Ø or 1Ø 6.4KVA
TDC 4885 3Ø or 1Ø 6.8KVA
TDC 4890 3Ø or 1Ø 7.2KVA
TDC 4895 3Ø or 1Ø 7.6KVA 400 x 630 x 680
TDC 48100 3Ø or 1Ø 8KVA
TDC 48110 3Ø or 1Ø 8.8KVA
TDC 48120 3Ø or 1Ø 9.6KVA
TDC 48130 3Ø or 1Ø 10.4KVA
TDC 48140 3Ø or 1Ø 11.2KVA
TDC 48150 3Ø or 1Ø 12KVA 440 x 750 x 1000
TDC 48160 3Ø or 1Ø 12.8KVA
TDC 48170 3Ø or 1Ø 13.6KVA
TDC 48180 3Ø or 1Ø 14.4KVA
TDC 48190 3Ø or 1Ø 15.2KVA
TDC 48200 3Ø or 1Ø 16KVA

* Please contact us separately for capacities above 1Ø 16 KVA.
* Special order specifications are manufactured separately
* This size may vary depending on the design