Standard Specifications and Characteristics
Capacity(KVA) | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | |
---|---|---|---|---|---|---|---|---|
General Specifications | Cooling method | forced air-cooled type | ||||||
Qualification for use | 100% Continuous Use | |||||||
Control method | Full Bridge full stop | |||||||
element for use | Bridge Diode Module | |||||||
Inverter control method | High frequency PWM control method 20㎑ | |||||||
ST/SW CUTTING SYSTEM | Non-pure synchronization reduction by pure semiconductors | |||||||
transformer insulation class | H species | |||||||
Input voltage | a constant number | 1st or 3rd prize | ||||||
rated voltage | Specified when purchasing 110V, 220V, 380V, 440V | |||||||
Voltage fluctuation range | ±10% | |||||||
Rated frequency | 50~60㎐ ±5% | |||||||
power factor | 0.80 LAG or higher | |||||||
Output voltage | a constant number | 1 phase 2 winding type, one phase three-wire | ||||||
rated voltage | Designated when purchasing 110V, 220V, 110V/220V | |||||||
Rated frequency | 50~60㎐ ±0.5% | |||||||
Voltage stability | Within ±2% | |||||||
Transient voltage fluctuation | ±5% | |||||||
Transient voltage response rate | 50 %-100% sudden load when returning within ±2% within 50ms | |||||||
Output voltage variable | ±5% or more | |||||||
waveform distortion | THD within 3% | |||||||
overload tolerance | No more than 10 minutes at 125% / 1 minute at 150% | |||||||
power factor | 0.8 LAG | |||||||
Noise | 55dB or less | 60dB or less | ||||||
Comprehensive efficiency | 83% or more | 85% or more | 88% or more | |||||
synchronous segmentation | Synchronous collection time | Within 4ms | ||||||
an articulatory gun | Inverter failure, overload, DC low voltage, manual switching | |||||||
a storage battery | Types | Specify at purchase time | ||||||
Power outage compensation time | Specify at purchase time | |||||||
Capacity | Specify at purchase time | |||||||
quantity | 16 Cell | |||||||
rated voltage | 192V | |||||||
the lowest voltage | 168V | |||||||
the maximum voltage | 216V | |||||||
Insulation characteristics | Insulation voltage | Apply for 1 minute with AC 1500V 60㎐ | ||||||
Insulation resistance | 5V or higher when measured with DC 500V Megger | |||||||
Temperature characteristics | Transformer flow | 125 DEG or less | ||||||
Other | 80 DEG or less | |||||||
an enclosure | paint color | 5Y 7/1 |
Standard Specifications and Characteristics
Capacity (KVA) |
Dimension | Weight (Kg) |
||
---|---|---|---|---|
Width | Depth | Hight | ||
2~5(external battery) | 340 | 615 | 700 | 110 |
2~5(ES18Ah*16EA embedded) | 420 | 700 | 780 | 200 |
7.5 ~10 | 450 | 800 | 950 | 190 |
15 ~20 | 550 | 950 | 1150 | 350 |
30~40 | 720 | 810 | 1425 | 500 |
50 | 800 | 900 | 1560 | 600 |