GPS®-800 3Φ uninterruptible power supply using the MODULE method of parallel operation

N+1 UPS Hot Swap Plug-In Module Capacity Expansion with a New Concept of Parallel
MODULE!

Overview

This is a modular UPS system based on a True Online  battery topology. The next generation UPS system introduces  an innovative  concept of UPS technology, comes with a variety of protection features, and always provides reliable and precise AC power to load equipment. Parallel redundancy allows configuration in 3/3, 3/1 or 1/1 systems .It consists of a  high-efficiency ALL IGBT and is lightweight, easy to transport and maintain, and can be installed in small spaces.

Features

  • Redundancy structure

  • Constant voltage, constant frequency, sine wave

  • Flexibility and scalability

  • High power density (volume/capacity)

  • Management and communication functions

  • Parallel operation (n +1) possible

  • Minimize user and environment-friendly system footprint

  • Save message status automatically (outputable-pc)

  • Check the voltage, current, and frequency of each area on the lcd

  • Minimize power consumption

* Option: SNMP functionality is purchased separately.

GPS-801 SERIES

GPS-801 SERIES(10KVA ~ 100KVA)

TECHNICAL SPECIFICATIONS

GPS-801 TECHNICAL DATA
Overview Systematic approach Online Battery, Double Conversion, VFI
Structure Modular parallel hot-plugged modules
Move it an unshakable motion
Input Input voltage 3 × 400 + N
Input allowable voltage -27 and + 20
Input current 3 × 15A – no inrush current at startup per module
Input power frequency 47 – 63
Initial operating time > 60
Input power factor 0.99
THDI(%) 5
Output Output 10kVA/8KW to 100kVA/80KW
Output frequency tolerance 50/60Hz ± 0.1%
Output Frequency Adjustment (Hz) ±1, ±2, ±3(selectable)
Output Frequency Rotation 1Hz/sec
Voltage(V) 3 × 400 + N
Static load output rate of variation (load holding) ±1%
Output Variation Rate at Unbalanced Loads ±1%(for 100% unbalanced loads)
Dynamic load output fluctuation rate (load fluctuation in stages up to 100%) ±2%
Overload tolerance 110%: 10 minutes, 125%: 60 seconds, 1000%: 1 cycle
Output waveform a sine curve
Output THD (%) Less than 2% at linear load
Load crest factor 6 : 1
AC – AC efficiency (nominal) 96%(with maximum load applied)
DC – AC Efficiency (nominal) 98%(with maximum load applied)
Battery DC-Link Voltage ±340 to ±425
quantity 64 × 12V
Type Sealed, lead acid, rechargeable
general details maximum power consumption(Po=8KW) N × 333W(N × 1136 BTU)
ambient temperature(÷C) -10 to +40(When running), -20 to +60(When storing)
relative humidity(%) maximum 95% (no condensation)
Altitude(m) 1500m(State without output degradation)
Enclosure IP20
Cooling method Speed ​​control multi-fan method(forced cooling)
standard specifications EMC EN50091 – 2 Class A : IEC 62040 – 2 Class A
Design EN50091 – 3 : IEC 62040 – 3
Safety EN50091 – 1 : IEC 62040 -1-1
Low magnetic field radiation EMF as per ICNIRP
Size UPS type (KVA) 10 20 30 40 50 60 70 80 90 100
Height (cm) 71 80 90 99 108 118 127 136 146 155
Width (cm) 59.8
Depth (cm) 67.3
Weight (kg) 84 99 114 129 144 159 174 189 204 219
Noise Noise (dBA)
50% Under load
48 52 53 54 55 55.8 56.4 57 57.5 58
Noise (dBA)
full Under load
51 54 55 57 58 58.8 59.4 60 60.5 61

*This size may vary slightly during design changes to improve quality.